Daikin Split, Outdoor unit Daikin RXM35N5V1B9, indoor unit Daikin FVXM35FV1B9

The indoor unit was running in full fan speed and had a faulty indoor unit leak detector sensor.

After replacing the leak detector sensor, you must follow the below steps to reset the indoor unit alarm.

A0-00 (FVXM-F reset method on Infrared controller)


Replace sensor to new one
 
Power On the unit
 
Clean last error :
 
Press “TEMP” and “MODE” bottoms at the same time
Press “ON/OFF” bottom for 5 sec
 
Power OFF and power ON the unit.
 
Go to “trial operation” (as explain in the manual)
 
Press “TEMP” and “MODE” bottoms at the same time
Press  “MODE” bottom 2 times and you will see 7 on the screen of the remocon.
 
Power OFF and power ON the unit.
 
Normal unit operation.